R-717 (Ammonia) Refrigerant Line Capacities

HVAC Systems & Components

R-717 (Ammonia) Refrigerant Line Capacities

Tons for 100 ft.

R-717 (Ammonia) Tons for 100 Ft.
Δp
IPS
Δp
-40
-20
0
20
40
3
2
Sch
0.31
0.49
0.73
1.06
1.46
3/4
80
-
-
-
2.6
3.8
-
-
1
-
-
2.1
3.4
5.2
7.6
13.9
106
1-1/4
40
3.2
5.6
8.9
13.6
19.9
36.5
229a
1-1/2
-
4.9
8.4
13.4
20.5
29.9
54.8
349a
2
-
9.5
16.2
26.0
39.6
57.8
106
811
2-1/2
-
15.3
25.9
41.5
63.2
92.1
168
1293
3
-
27.1
46.1
73.5
112
163
298
2288
4
-
55.7
94.2
150
229
333
600
4662
5
-
101
170
271
412
601
1095
-
6
-
164
276
439
668
972
1771
-

 

  • Adapted from ASHRAE HVAC Refrigeration Handbook
  • Schedule 80 Pipe