Totally Enclosed Fan-Cooled Induction Motors Efficiencies

Electric Motors, Generators and Drives

This table defines the nominal efficiencies for totally enclosed fan-cooled induction motors that ar rate at 600 V or less (Random Wound).

An AC induction or asynchronous motor is an electric motor where the electric current in the rotor needed to produce torque is obtained by electromagnetic induction from the magnetic field of the stator winding.

Nominal Efficiencies for Totally Enclosed Fan-Cooled Induction Motors

hp

Totally Enclosed Fan-Cooled

1200 RPM (6-pole)

1800 RPM (4-pole)

3600 RPM (2-pole)

EPAct*

NEMA Premium

EPAct*

NEMA Premium

EPAct*

NEMA Premium

1

80.0

82.5

82.5

85.5

75.5

77.0

1.5

85.5

87.5

84.0

86.5

82.5

84.0

2

86.5

88.5

84.0

86.5

84.0

85.5

3

87.5

89.5

87.5

89.5

85.5

86.5

5

87.5

89.5

87.5

89.5

87.5

88.5

7.5

89.5

91.0

89.5

91.7

88.5

89.5

10

89.5

91.0

89.5

91.7

89.5

90.2

15

90.2

91.7

91.0

92.4

90.2

91.0

20

90.2

91.7

91.0

93.0

90.2

91.0

25

91.7

93.0

92.4

93.6

91.0

91.7

30

91.7

93.0

92.4

93.6

91.0

91.7

40

93.0

94.1

93.0

94.1

91.7

92.4

50

93.0

94.1

93.0

94.5

92.4

93.0

60

93.6

94.5

93.6

95.0

93.0

93.6

75

93.6

94.5

94.1

95.4

93.0

93.6

100

94.1

95.0

94.5

95.4

93.6

94.1

125

94.1

95.0

94.5

95.4

94.5

95.0

150

95.0

95.8

95.0

95.8

94.5

95.0

200

95.0

95.8

95.0

96.2

95.0

95.4

250

-

95.8

-

96.2

-

95.8

300

-

95.8

-

96.2

-

95.8

350

-

95.8

-

96.2

-

95.8

400

-

95.8

-

96.2

-

95.8

450

-

95.8

-

96.2

-

95.8

500

-

95.8

-

96.2

-

95.8

Contribute Article